TORPEDO

Wet-type vaporizer ES

Water bath, electrically heated, cabinet design · Propane / LPG

rDME-compatible on request

Design
Wet-type vaporizer, electrically heated (water bath)
Medium
Propane / LPG, rDME on request
Capacity
60–1,400 kg/h
Shape
cabinet, heat transfer medium: inhibited antifreeze/water mixture
Pressure rating
PN 25, test pressure 36 bar
Connections
to customer specification
Explosion protection
Zones 1 and 2, PTB-tested; control cabinet outside the hazardous area
Safety technology
SIL 2 capable
Codes and standards
PED 2014/68/EU, AD 2000-Merkblatt HP 801 No. 25

Send an enquiry LPG brochure

Wet-type vaporizer ES in cabinet design

How it works

The TORPEDO liquefied petroleum gas (LPG) vaporizer type ES is a wet-type vaporizer. It is indirectly electrically heated and works with a liquid heat transfer medium based on a mixture of antifreeze, inhibitors and water.

The vaporizer coil and the heating element terminal box are flanged to the front end of the vaporizer and can be withdrawn for servicing. The vaporizer is started up electrically from the control cabinet. The heat transfer medium is heated and monitored under thermostat control within preset limits.

Once the required vaporization temperature has been reached, the solenoid valves open. LPG enters the vaporizer and is converted into the vapour phase there at unchanged pressure up to the stated rated capacity.

In the event of overload, power failure or severe voltage fluctuations, the solenoid valves close. An additional safety temperature limiter monitors the heat transfer medium and prevents its temperature from rising to an impermissible level. The design and construction of the vaporizer ensure low-maintenance and fully automatic vaporizer operation, including in hazardous area Zones 1 and 2; the control cabinet is installed outside the hazardous area. The unit can be integrated into SIL 2 safety functions.

Sizes

TypeRated capacity
kg/h
Connected load
kW
W × H × L
mm
Empty weight approx.
kg
ES 606013385 × 1185 × 590100
ES 10010019435 × 1280 × 730110
ES 20020037535 × 1295 × 845240
ES 30030055535 × 1660 × 845310
ES 40040073535 × 1660 × 845320
ES 50050091535 × 1885 × 1195430
ES 60060091535 × 1885 × 1195470
ES 700700113.5535 × 2030 × 1195540
ES 800800113.5535 × 2030 × 1195550
ES 10001,000181on request990
ES 14001,400227on requeston request

Voltage 400 V. The rated capacity applies at saturation conditions to propane, butane and rDME alike. Values for the standard version; we adapt wet-type vaporizers to the order and the place of use, also with combined heating (electric and heating water).

Same design for ammonia (NH₃) Wet-type vaporizer ESA · 30–320 kg/h

To size your vaporizer, we need some details about gas, storage and operation: Planning notes for propane / LPG →

Planning a gas supply system?

We advise you on sizing, from the first question to the turnkey station.

We look forward to your enquiry:

info@torpedo-online.de

04106 / 62 77-0